DTC B0223, B0233, B023A, or B0408
Diagnostic Instructions
DTC Descriptor
DTC B0223 01: Recirculate Position Command 1 Circuit Short to Battery
DTC B0223 06: Recirculate Position Command 1 Circuit Low Voltage/Open
DTC B0233 01: Air Flow Control Circuit Short to Battery
DTC B0233 06: Air Flow Control Circuit Low Voltage/Open
DTC B023A 02: HVAC Actuators Supply Voltage Short to Ground
DTC B0408 01: Main Temperature Control Circuit Short to Battery
DTC B0408 06: Main Temperature Control Circuit Low Voltage/Open
Diagnostic Fault Information
Circuit
| Short to Ground
| Open/High Resistance
| Short to Voltage
| Signal Performance
|
Stepper Motors 12V Reference
| B023A 02, B0223 06, B0233 06, B0408 06
| B0223 06, B0233 06, B0408 06
| --
| --
|
Recirculation Actuator Control 1
| B0223 06
| B0223 06
| B0223 01
| 1
|
Recirculation Actuator Control 2
| B0223 06
| B0223 06
| B0223 01
| 1
|
Recirculation Actuator Control 3
| B0223 06
| B0223 06
| B0223 01
| 1
|
Recirculation Actuator Control 4
| B0223 06
| B0223 06
| B0223 01
| 1
|
Air Temperature Actuator - Left Control 1
| B0408 06
| B0408 06
| B0408 01
| 2
|
Air Temperature Actuator - Left Control 2
| B0408 06
| B0408 06
| B0408 01
| 2
|
Air Temperature Actuator - Left Control 3
| B0408 06
| B0408 06
| B0408 01
| 2
|
Air Temperature Actuator - Left Control 4
| B0408 06
| B0408 06
| B0408 01
| 2
|
Mode Actuator Control 1
| B0233 06
| B0233 06
| B0233 01
| 3
|
Mode Actuator Control 2
| B0233 06
| B0233 06
| B0233 01
| 3
|
Mode Actuator Control 3
| B0233 06
| B0233 06
| B0233 01
| 3
|
Mode Actuator Control 4
| B0233 06
| B0233 06
| B0233 01
| 3
|
1. Air Recirculation Malfunction
2. Air Temperature Malfunction
3. Air Distribution Malfunction
|
Circuit/System Description
Stepper motors are used for temperature regulation, air distribution control and recirculation flap control.
With the appropriate switches at the HVAC controls, the desired air temperature flap position, air distribution flap position and recirculation flap position can be put in. The selected values are passed to the HVAC control module via the LIN-Bus. The HVAC control module supplies a 12 V reference voltage to the stepper motors and energises the 4 stepper motor coils with a pulsed ground signal. The stepper motors put the appropriate flap into the calculated position, in order to reach the put in temperature/position.
Conditions for Running the DTC
• | The HVAC control module is ON. |
Conditions for Setting the DTC
B023A 02
The stepper motors supply output is shorted to ground.
B0223 01, B0233 01 or B0408 01
At least one control output (of 4 possible outputs) of the appropriate stepper motor is shorted to voltage when motor starts moving. Faults are not detected when motor is already running or target position is already reached.
B0223 06, B0233 06 or B0408 06
At least one control output (of 4 possible outputs) of the appropriate stepper motor is shorted to ground or open when motor starts moving. Faults are not detected when motor is already running or target position is already reached.
Action Taken When the DTC Sets
B023A 02
• | The affected output will be switched off for hardware protection. |
• | All stepper motors are deactivated. |
B0223, B0233 or B0408
• | The affected output will be switched off for hardware protection. |
• | The affected stepper motor is deactivated. |
Conditions for Clearing the DTC
The condition for setting the DTC is no longer present.
Reference Information
Schematic Reference
HVAC Schematics : Automatic
Connector End View Reference
Component Connector End Views
Description and Operation
Automatic HVAC Description and Operation
Electrical Information Reference
Scan Tool Reference
Control Module References for scan tool information
Circuit/System Verification
- Verify that DTC B023A 02 is not present.
⇒ | If DTC B023A is present |
| Refer to Actuator Power Supply Malfunction. |
⇓ | If DTC B023A is not present |
- Verify that DTC B0223 01 or B0223 06 is not present.
⇒ | If DTC B0223 is present |
| Refer to Recirculation Actuator Malfunction. |
⇓ | If DTC B0223 is not present |
- Verify that DTC B0233 01 or B0233 06 is not present.
⇒ | If DTC B0233 is present |
| Refer to Mode Actuator Malfunction. |
⇓ | If DTC B0233 is not present |
- Verify that DTC B0408 01 or B0408 06 is not present.
⇒ | If DTC B0408 is present |
| Refer to Air Temperature Actuator Malfunction. |
⇓ | If DTC B0408 is not present |
- All OK.
Circuit/System Testing
Actuator Power Supply Malfunction
- Ignition OFF, disconnect the X3 harness connector at the K33 HVAC Control Module.
- Test for infinite resistance between the reference voltage circuit terminal 15 X3 and ground.
⇒ | If less than infinite resistance |
| Repair the short to ground on the circuit. |
- Replace the K33 HVAC Control Module.
Recirculation Actuator Malfunction
- Ignition OFF, disconnect the X3 harness connector at the K33 HVAC Control Module and at the M46 Air Recirculation Door Actuator.
- Ignition ON, test for less than 0.3 V between the control circuit terminal at the K33 HVAC Control Module harness connector listed below and ground:
| Repair the short to voltage on the circuit. |
- Ignition OFF, test for infinite resistance between the control circuit terminal at the K33 HVAC Control Module harness connector listed below and ground:
⇒ | If less than infinite resistance |
| Repair the short to ground on the circuit. |
- Test for less than 5 Ω between the control circuit terminals listed below:
• | M46 Air Recirculation Door Actuator terminal 1 and terminal 16 X3 at the K33 HVAC Control Module harness connector |
• | M46 Air Recirculation Door Actuator terminal 2 and terminal 15 X3 at the K33 HVAC Control Module harness connector |
• | M46 Air Recirculation Door Actuator terminal 3 and terminal 17 X3 at the K33 HVAC Control Module harness connector |
• | M46 Air Recirculation Door Actuator terminal 4 and terminal 18 X3 at the K33 HVAC Control Module harness connector |
• | M46 Air Recirculation Door Actuator terminal 6 and terminal 19 X3 at the K33 HVAC Control Module harness connector |
| Repair the open/high resistance in the circuit. |
- Replace the M46 Air Recirculation Door Actuator and verify the DTC does not reset.
| Replace the K33 HVAC Control Module. |
- All OK.
Mode Actuator Malfunction
- Ignition OFF, disconnect the X3 harness connector at the K33 HVAC Control Module and at the M37 Mode Door Actuator.
- Ignition ON, test for less than 0.3 V between the control circuit terminal listed below and ground:
| Repair the short to voltage on the circuit. |
- Ignition OFF, test for infinite resistance between the control circuit terminal listed below and ground:
⇒ | If less than infinite resistance |
| Repair the short to ground on the circuit. |
- Test for less than 5 Ω between the control circuit terminals listed below:
• | M37 Mode Door Actuator terminal 1 and terminal 2 X3 at the K33 HVAC Control Module harness connector |
• | M37 Mode Door Actuator terminal 2 and terminal 15 X3 at the K33 HVAC Control Module harness connector |
• | M37 Mode Door Actuator terminal 3 and terminal 3 X3 at the K33 HVAC Control Module harness connector |
• | M37 Mode Door Actuator terminal 4 and terminal 4 X3 at the K33 HVAC Control Module harness connector |
• | M37 Mode Door Actuator terminal 6 and terminal 5 X3 at the K33 HVAC Control Module harness connector |
| Repair the open/high resistance in the circuit. |
- Replace the M37 Mode Door Actuator and verify the DTC does not reset.
| Replace the K33 HVAC Control Module. |
- All OK.
Air Temperature Actuator Malfunction
- Ignition OFF, disconnect the X3 harness connector at the K33 HVAC Control Module and at the M6L Air Temperature Door Actuator - Left.
- Ignition ON, test for less than 0.3 V between the control circuit terminal listed below and ground:
| Repair the short to voltage on the circuit. |
- Ignition OFF, test for infinite resistance between the control circuit terminal listed below and ground:
⇒ | If less than infinite resistance |
| Repair the short to ground on the circuit. |
- Test for less than 5 Ω between the control circuit terminals listed below:
• | M6L Air Temperature Door Actuator - Left terminal 1 and terminal 11 X3 at the K33 HVAC Control Module harness connector |
• | M6L Air Temperature Door Actuator - Left terminal 2 and terminal 15 X3 at the K33 HVAC Control Module harness connector |
• | M6L Air Temperature Door Actuator - Left terminal 3 and terminal 12 X3 at the K33 HVAC Control Module harness connector |
• | M6L Air Temperature Door Actuator - Left terminal 4 and terminal 13 X3 at the K33 HVAC Control Module harness connector |
• | M6L Air Temperature Door Actuator - Left terminal 6 and terminal 14 X3 at the K33 HVAC Control Module harness connector |
| Repair the open/high resistance in the circuit. |
- Replace the M6L Air Temperature Door Actuator - Left and verify the DTC does not reset.
| Replace the K33 HVAC Control Module. |
- All OK.
Repair Instructions
Perform the Diagnostic Repair Verification after completing the diagnostic procedure.