To the top of the document
Spark
   
GMDE Start Page Load static TOC Load dynamic TOC Help?

Testing for Short to Ground

Caution: Refer to Test Probe Caution in the Preface section.

The following procedures test for a short to ground in a circuit.

With a Digital Multimeter (DMM)

  1. Remove the power feed (i.e. fuse, control module) from the suspect circuit.
  2. Disconnect the load.
  3. Set the rotary dial of the DMM to the Ω position.
  4. Connect one lead of the DMM to one end of the circuit to be tested.
  5. Connect the other lead of the DMM to a good ground.
  6. If the DMM does NOT display infinite resistance (OL), there is a short to ground in the circuit.

With a Test Lamp

  1. Remove the power feed (i.e. fuse, control module) from the suspect circuit.
  2. Disconnect the load.
  3. Connect one lead of the test lamp to battery positive voltage.
  4. Connect the other lead of the test lamp to one end of the circuit to be tested.
  5. If the test lamp illuminates, there is a short to ground in the circuit.

Fuse Powering Several Loads

  1. Review the system schematic and locate the fuse that is open.
  2. Open the first connector or switch leading from the fuse to each load.
  3. Connect a DMM across the fuse terminals (be sure that the fuse is powered).
  4. • When the DMM displays voltage the short is in the wiring leading to the first connector or switch.
    • If the DMM does not display voltage refer to the next step.
  5. Close each connector or switch until the DMM displays voltage in order to find which circuit is shorted.
   


© Copyright Chevrolet. All rights reserved