Refrigerant Recovery and Recharging - High Voltage Electric Compressor

Special Tools

    • GE 43600 Hybrid A/C Oil Injector Adapter Hose
    • GE-45037-A A/C Oil Injector
    • GE-48800 CoolTech A/C Recharge Machine
    • GE 48997 Hybrid A/C Oil Injector Adapter Hose

For equivalent regional tools, refer to Special Tools .

Danger: This A/C system's high voltage A/C Compressor uses Polyolester (POE) refrigerant oil. Use of any refrigerant oil other than POE may result in compressor failure and/or loss of high voltage isolation which may result in serious danger or death. For applicable equipment please refer to TIS Newsletter/repair equipment information.

Warning: To prevent personal injury, avoid breathing A/C Refrigerant and lubricant vapour or mist. Work in a well ventilated area. To remove refrigerant from the A/C System, use service equipment designed for recovery that is certified to meet the requirements of the appropriate SAE Standards. If an accidental system discharge occurs, ventilate the work area before continuing service. Additional health and safety information may be obtained from the refrigerant, refrigerant recovery, and lubricant manufacturers.

Warning: For personal protection, goggles and lint-free gloves should be worn and a clean lint free cloth wrapped around fittings, valves, and connections when doing work that includes opening the refrigerant system. If refrigerant comes in contact with any part of the body severe frostbite and personal injury can result. The exposed area should be flushed immediately with cold water and prompt medical help should be obtained.

Caution: This A/C refrigerant system is equipped with a High Voltage electric A/C compressor and you must replace the desiccant if the A/C refrigerant system has been open to atmosphere for more than thirty minutes, or if the A/C refrigerant oil has been contaminated. Failure to replace the desiccant will result in damage to the A/C refrigerant system.

Caution: R-134a is the only approved refrigerant for use in this vehicle. The use of any other refrigerant may result in poor system performance or component failure and potentially void the vehicle warranty for the refrigerant system.

Caution: Do not lubricate A/C line seal washers as mineral oil will damage the seal and cause leaks. Use only 525 viscosity mineral oil to lubricate o-rings as well as fitting threads for the prevention of fitting seizure.

Caution: Failure to flush the refrigerant recovery recharge equipment hoses before adding refrigerant to a hybrid vehicle with an electric compressor may result in an unacceptable amount of Polyalkylene Glycol (PAG) oil entering the refrigerant system. This could result in reduced electrical resistance of the Polyolester (POE) oil and reduce its ability to provide the required level of high voltage isolation.

Both the GE 43600 Hybrid A/C Oil Injector Adapter Hose and GE-48800 CoolTech A/C Recharge Machine are a complete air conditioning service centre for R-134a. The ACR 2000 recovers, recycles, evacuates and recharges A/C refrigerant quickly, accurately and automatically. The unit has a display screen that contains the function controls and displays prompts that will lead the technician through the recover, recycle, evacuate and recharge operations. R-134a is recovered into and charged out of an internal storage vessel. Both units automatically replenish this vessel from an external source tank in order to maintain a constant 5.45-6.82 kg (12-15 lbs) of A/C refrigerant.

The ACR 2000 has a built in A/C refrigerant identifier that will test for contamination, prior to recovery and will notify the technician if there are foreign gases present in the A/C system. If foreign gases are present, the ACR 2000 will not recover the refrigerant from the A/C system.

The ACR 2000 also features automatic air purge, single pass recycling and an automatic oil drain.

GE-48800 CoolTech A/C Recharge Machine is released as a required replacement for the previously essential GE 43600 Hybrid A/C Oil Injector Adapter Hose . The GE-48800 CoolTech A/C Recharge Machine is SAE J2788 compliant and meets GM requirements for A/C Refrigerant System Repairs on all General Motors vehicles, including Hybrid systems with Polyolester (POE) refrigerant oil.

Refer to the GE 43600 Hybrid A/C Oil Injector Adapter Hose and GE-48800 CoolTech A/C Recharge Machine ACR 2000 manual for operation and setup instruction. Always recharge the A/C System with the correct amount of R-134a. Refer to Refrigerant System Specifications for the correct amount.

A/C Refrigerant System Oil Charge Replenishing

If oil was removed from the A/C system during the recovery process or due to component replacement, the oil must be replenished. If no oil was removed from the A/C system during recovery, do not charge any POE oil into the A/C system. POE refrigerant oil can be injected into a charged A/C system using GE-45037-A injector along with GE 48997 adapter . For the proper quantities of oil to add to the A/C refrigerant system, refer to Refrigerant System Specifications .

   